U-Match Series Service Manual
67
GUHN36NM3HO + + GKH36K3HI
. Power cord 5×1.5 mm
2
(H07RN-F)
. Power cord 3×1.0 mm
2
(H05VV-F)
. Communication Cords 2×0.75 mm
2
(H05VV-F)
GUHN42NM3HO + GKH42K3HI
GUHN48NM3HO + GKH48K3HI
GUHN60NM3HO + GKH60K3HI
. Power cord 5×2.5 mm
2
(H07RN-F)
. Power cord 3×1.0 mm
2
(H05VV-F)
. Communication Cords 2×0.75 mm
2
(H05VV-F)
Figure 3-2-10
(5) Electric wiring of indoor unit side
Remove the electric box cover from the electric box sub-assy and then connect the wire.
Duct Type Unit
L
N
1
2
H1
H2
Figure 3-2-11
The F, C, O connect to the COMMOM, CLOSE and OPEN terminal of the fresh air valve
respectively.
Cassette Type Unit
18k
24~60k
Figure 3-2-12
CAUTION!
. The power cord and the wire of the fresh air valve are high-voltage, while the communication cord and connection
wire of the wired controller are low-voltage. They should run separately against electromagnetic interference.
. The high-voltage and low-voltage lines should pass through the rubber rings at different electric box covers.
. Do not bundle the connection wire of the wired controller and the communication cord together, or arrange them in
parallel, otherwise improper operation would occur.
. The high-voltage and low-voltage lines should be fixed separately and securely, with internal big clamps for the former
and small clamps for the latter.