DC Inverter Multi VRF System
12
Fig.8
Total capacity of downstream indoor units C (kW)
Gas pipemm
Liquid pipemm
C 5.6
Φ12.7
Φ6.35
5.6C14.2
Φ15.9
Φ9.52
14.2C22.4
Φ19.05
Φ9.52
22.4C33.5
Φ25.40
Φ12.70
4.2.6 Dimension of Pipe between Indoor Branch and IDU
Dimension of pipe between indoor branch and IDU should be consistent with the dimension of
indoor pipe.
Fig. 9