GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
201
2.2.4.86 HL Fan drive DC bus low voltage protection
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If HL is displayed, it indicates fan
drive DC bus low voltage protection
Possible reason
Power supply voltage is lower than 320V;
Fan drive board is abnormal.
Troubleshooting:
2.2.4.87 HJ Failure startup of inverter fan
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If HJ is displayed, it indicates Failure
startup of inverter fan
Possible reason
Poor contact of fan UVW wire
Fan is broken
Fan blade is blocked (Fan blade is blocked and motor shaft is rusty)
■Fan drive board is abnormal