GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
217
Make sure the IDUs connected with one wired controller belong to the same series.
2.2.4.105 LC Mismatch of IDU and ODU models
Error display:
IDU wired controller and IDU receive light board will display
Error judgment condition and method:
When some IDUs or devices which cannot be identified by some ODUs are installed in the system,
mismatch error of IDU and ODU models will occur.
Possible reason
Mismatch of IDU and ODU
Troubleshooting:
When some IDUs or devices which cannot be identified by some ODUs are installed in the system
(E.g. floor heating device is installed in modular DC inverter multiple VRF system), the error will occur.
Please remove the relevant IDU devices or replace the ODU with suitable model.
2.2.4.106 n0 System energy-saving operation setting status
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
This code is function setting status code, which indicates that the system has entered energy-saving
setting status. 00 is the control with priority of comfort; 01 is the control with priority of energy savings,
in which energy savings can reach 15%.
Possible reason——
Troubleshooting:
status code, no troubleshooting.
2.2.4.107 n2 Upper limit setting status of IDU&ODU capacity configuration ratio
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
This code is function setting status code, which indicates that the system has entered upper limit
setting status of IDU&ODU capacity configuration ratio.
Possible reason——
Troubleshooting:
status code, no troubleshooting.
2.2.4.108 n4 Limit setting status of max output capacity
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:

Table of Contents

Other manuals for Gree GMV-280WM/E-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-280WM/E-X and is the answer not in the manual?

Gree GMV-280WM/E-X Specifications

General IconGeneral
BrandGree
ModelGMV-280WM/E-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals