GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
220
2.2.4.117 nF Fan only model status
Error display:
ODU mainboard will display
Error judgment condition and method:
This code is the fan only model status code, which indicates that the system has been set to fan
only unit status. The IDUs can only operate in fan mode.
Possible reason——
Troubleshooting:
status code, no troubleshooting.
2.2.4.118 P0 Compressor drive board error
Error display:
IDU wired controller will display
Error judgment condition and method:
Check error code through IDU wired controller. If IDU wired controller displays P0, please also
check the error code displayed on the nixie tube of ODU main control board. Detailed error of
compressor drive board can be judged according to the error code on main control board. Then arrange
troubleshooting accordingly.
Possible reason
Compressor drive module reset protection (P3 is displayed on the nixie tube of ODU main control
board)
Compressor drive temperature sensor error (P7 is displayed on the nixie tube of ODU main control
board)
Compressor drive IPM high temperature protection (P8 is displayed on the nixie tube of ODU main
control board)
Compressor drive current detecting circuit error (PC is displayed on the nixie tube of ODU main
control board)
Compressor drive charging circuit error (PF is displayed on the nixie tube of ODU main control
board)
Inverter compressor non-synchronism protection (P9 is displayed on the nixie tube of ODU main
control board)
Inverter compressor startup failure (PJ is displayed on the nixie tube of ODU main control board)
Troubleshooting:
Find out corresponding solution according to the error code displayed on ODU mainboard.
2.2.4.119 P1 Compressor drive board operation error
Error display:
IDU wired controller will display
Error judgment condition and method:
Check error code through IDU wired controller. If IDU wired controller displays P1, please also
check the error code displayed on the nixie tube of ODU main control board. Detailed error of

Table of Contents

Other manuals for Gree GMV-280WM/E-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-280WM/E-X and is the answer not in the manual?

Gree GMV-280WM/E-X Specifications

General IconGeneral
BrandGree
ModelGMV-280WM/E-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals