GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
222
Troubleshooting:
2.2.4.122 P5 Inverter compressor overcurrent protection
Error display:
ODU mainboard will display
Error judgment condition and method:
Check the error code on nixie tube of ODU main control board. If P5 is displayed, it indicates
inverter compressor overcurrent protection
Possible reason
Poor contact of compressor UVW wire;
Connection sequence of compressor UVW wire is wrong;
Compressor is broken;
System is blocked;
Compressor drive board IPM module is broken.