GMV DC Inverter VRF 
39 
 
Fig. 4.6.1 
4.6.2 Communication mode 8  
CAN bus mode is taken for communication between IDU and ODU and communication 
among IDUs. 
4.6.3 Selection and connection mode of communication material 
4.6.3.1 Select communication material 
Note:  if  air  conditioners  are  installed  at  places  where  there’s  strong  electromagnetic 
interference, the communication wire of IDU and wired controller must use shielded wire and 
the communication wire between IDU and IDU/ODU must use shielded twisted pair. 
(1) Select communication wire between IDU and wired controller 
Total length of 
communication line 
between IDU unit and 
wired controller L (m)   
Light/Ordinary   
polyvinyl chloride   
sheathed cord. 
(60227 IEC 52 
/60227 IEC 53) 
1. Total length of communication line can't 
exceed 250m. 
2. The cord shall be Circular cord (the cores 
shall be twisted together). 
3. If unit is installed in places with intense 
magnetic field or strong interference, it is 
necessary to use shielded wire.