EasyManua.ls Logo

Gree GMV-335WM/E-X - Page 161

Gree GMV-335WM/E-X
308 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GREE GMV5E DC INVERTER VRF UNITS SERVICE MANUAL
157
2.2.4.28C2 main control and inverter compressor drive communication error
Error display:
ODU mainboard, IDU wired controller and IDU receive light board will
display
Error judgment condition and method:
If ODU hasnt received inverter compressor drive board data in continuous 30s, report the error.
Possible reason
Communication wire between ODU mainboard inside module and inverter compressor drive board
is not connected properly
Inverter compressor drive board is abnormal
Mainboard is abnormal

Table of Contents

Other manuals for Gree GMV-335WM/E-X

Related product manuals