D.C. Inverter Multi VRF Modular 
25 
4.2.5.5 Manifold at indoor unit side 
Manifold at indoor unit side can be selected as per total capacity of downstream indoor unit(s). 
Refer to the following table. 
 
Fig.28 
Total capacity of downstream indoor 
unit(s) C (kW) 
4.2.5.6 Fitting pipe between manifolds   
Pipe  size  (between  two  manifolds  at  indoor  unit  side)  is  based  on  the  total  capacity  of 
upstream indoor unit(s). 
 
Fig.29 
Total capacity of downstream indoor 
unit(s) C(kW) 
Dimension of the pipe of indoor branch