D.C. Inverter Multi VRF Modular
33
Model
Basic models
Circuit
breaker
capacity
(A)
Circuit breaker
capacity for
combined
units (A
)
Wire size of
power supply
(mm
2
)
Wire size of
combined uni (mm
2
)
GMV-2016WM/B-X
280+560+560+615
200
25+63+63+63
2.5+10+10+10
2.5
×
5+10
×
5+10
×
5+10
×
5
GMV-2072WM/B-X
280+ 560+615+615
200
25+63+63+63
2.5+10+10+10
2.5
×
5+10
×
5+10
×
5+10
×
5
GMV-2128WM/B-X
280+615+615+615
200
25+63+63+63
2.5+10+10+10
2.5
×
5+10
×
5+10
×
5+10
×
5
GMV-2184WM/B-X
335+615+615+ 615
200
32+63+63+63
4.0+10+10+10
4.0
×
5+10
×
5+10
×
5+10
×
5
GMV-2240WM/B-X
400+615+615+615
200
40+63+63+63
6.0+10+10+10
6.0
×
5+10
×
5+10
×
5+10
×
5
GMV-2295WM/B-X
450+615+615+615
225
40+63+63+63
6.0+10+10+10
6.0
×
5+10
×
5+10
×
5+10
×
5
GMV-2350WM/B-X
504+615+615+615
225
50+63+63+63
10+10+10+10
10
×
5+10
×
5+10
×
5+10
×
5
GMV-2405WM/B-X
560+615+615+615
225
63+63+63+63
10+10+10+10
10
×
5+10
×
5+10
×
5+10
×
5
GMV-2460WM/B-X
615+615+615+615
225
63+63+63+63
10+10+10+10
10
×
5+10
×
5+10
×
5+10
×
5
Note:“280+400”: indicates the combination of GMV-280WM/B-X and GMV-400WM/B-X unit.
Please refer to the following table for circuit breaker and circuit breaker for indoor units.
Breaker listed in the table represents total capacity of breaker in one system.
Total capacity of indoor
units
Capacity of circuit breaker
(A)
Min. sectional area of
power cord (mm
2
)
Min. sectional area of
grounding wire (mm
2
)
Below10A
10
1.0
1.0
16~10A
16
1.5
1.5
20~16A
20
2.5
2.5
32~20A
32
4.0
4.0
Total capacity of indoor
units
Capacity of circuit breaker
(A)
Min. sectional area of
power cord (mm
2
)
Min. sectional area of
grounding wire (mm
2
)
40~32A
40
6.0
6.0
50~40A
50
10.0
10.0
63~50A
63
16.0
16.0
80~63A
80
25.0
16.0
100~80A
100
35.0
16.0
125~100A
125
50.0
25.0
Breaker capacity and power cord specification for every indoor unit
Indoor unit
Capacity of circuit breaker
(A)
Min. sectional area of
grounding wire (mm
2
)
Min. sectional area of
power cord (mm
2
)
Wall-mounted type
6
1.0
1.0
Duct type unit (heat pump)
6
1.0
1.0
Cassette type unit (heat
pump)
6
1.0
1.0
One-way cassette type
unit
6
1.0
1.0

Other manuals for Gree GMV-450WM/B-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree GMV-450WM/B-X and is the answer not in the manual?

Gree GMV-450WM/B-X Specifications

General IconGeneral
BrandGree
ModelGMV-450WM/B-X
CategoryAir Conditioner
LanguageEnglish

Related product manuals