GREE                                                                                          GMV5 INDOOR UNIT SERVICE MANUAL   
 
137 
 
1.2.9 “dC” Capacity DIP switch setting error 
Error display: 
IDU wired controller and IDU receive light board will display
 
Error judgment condition and method: 
If capacity DIP switch is set to the wrong position, report the error. 
Possible reason:   
■Capacity DIP switch is set to the wrong position 
■Detecting circuit is abnormal 
Troubleshooting: 
 
1.2.10 “dL” Air outlet temperature sensor error 
Error display: 
IDU wired controller and IDU receive light board will display
 
Error judgment condition and method: 
Sample the AD value of temperature sensor through temperature sensor detecting circuit and judge 
the  range  of  AD  value. If  the  sampling AD  value  exceeds  upper limit  and  lower limit  in  5  seconds 
continuously, report the error 
Possible reason:   
■Poor contact between air outlet temperature sensor and terminal in mainboard interface 
■Air outlet temperature sensor is abnormal 
■Detecting circuit is abnormal 
Troubleshooting: