GMV Heat Recovery DC Inverter VRF
56
Fig.4.2.1
(2) When starting up the debugging, the system automatically selects the operating mode
according to the current ambient temperature.
(3) When debugging, the front panel of the outdoor unit must be completely closed, otherwise it
will affect the accuracy of debugging (as shown in the Fig. as below).
Fig.4.2.2
(4) Display instruction for each stage progress at the time of debugging:
Instruction for each stage progress at the time of debugging
—
Meaning
Progress
Code
Display
Code
Display
Code
Display
01_ set up
master unit
db ON 01 ON CC ON
The system hasn’t set master module.
db ON 01 ON CF ON
The system has set more than 2
master modules. It needs to reset it.
db ON 01 ON OC ON
Master module setting is succeeded. It
will automatically enter into the next
02_ allocate
addresses
db ON 02 ON Ad Flash
The system is conducting the address
assignment.
db ON 02 ON OC ON
Address assignment is succeeded. It
will automatically enter into the next