Air Source Heat Pump Water Heater
22
Model Power Supply
2
Air
Switch
(A)
GRS-1.5/TD150ANbA-K
220-240V
~50Hz
1.5 1.5 1.5 16
(10) To be in compliance with EN 61000-3-11, impedance value of
power-supply system connected to product must be less than or equal to
the allowable maximum value of │Zsys│in the following sheet:
models max │Zsys│ unit: ohms
GRS-1.5/TD150ANbA-K 0.281
Before connecting the product to public power network, please consult your
local power supply authority to ensure that power network has met the above
requirements. No requirement for the unlisted product's impedance value of
power-supply system.
NOTICE!
① Only copper power cable is allowed and the working temperature shall not
exceed the specified set point.
② When the power cable is longer than 15m, its sectional area shall be
enlarged in case of accidents caused by overload.
③ The specifications of the power cable listed above is for the BV single-wire
(2~4 pieces) cable used at 40°C. The specification of the air switch listed
above is for the type D air switch used at 40°C.
④ When the actual working condition changes, please reselect the proper
power cable and air switch in accordance with their user’s manuals.