4.3.2.2 Screw Connection
Pipe diameter (inch)
Tightening torque (N·m)
Φ1/4
15-30
Φ3/8
35-40
Φ1/2
45-50
Φ5/8
60-65
Φ3/4
70-75
Φ7/8
80-85
4.4 Condensate Removal
(1) It is not allowed to connect the condensate drain pipe into waste pipe or other
pipelines which are likely to produce corrosive or peculiar smell to prevent the
smell from entering indoors or corrupt the unit.
(2) It is not allowed to connect the condensate drain pipe into rain pipe to prevent
rain water from pouring in and cause property loss or personal injury.
(3) Condensate drain pipe should be connected into special drain system for air
conditioner.
(4) The drain pan has primary and secondary drain connection. Condensate
removal is performed by attaching a 3/4” PVC pipe to the evaporator coil pan