DC Inverter U-match Series Duct Type Unit   
26 
(2)   Do not bend the pipes in an angle more than 90°. 
(3)   If the pipe is repeatedly bent or extended, it will become hard and difficult 
to be bent or extended. So do not bend or extend the pipe for more than 3 
times. 
(4)   When bending the pipe, do not bend it 
excessively,  otherwise 
broken. As shown beside, use a sharp 
cutter to cut the heat insulating pipe 
and bend it after the pipe is exposed. 
After bending, place the heat insulating 
pipe back on the pipeline and fix it with 
adhesive tape. 
 
3.2.3.4 Connection Pipe of Indoor and Outdoor Units 
NOTES! 
(1)  Connect the pipe to the unit. Please follow the instructions stated in the figures 
below. Use both spanner and torque wrench. 
(2)  When connecting the tapered screw nut, first apply chilled machine oil on its 
inner and outer surface and then screw it up for 3~4 circles. 
(3)  Confirm the tightening torque by referring to the following table (If the screw nut 
is over-twisted, it may be damaged and cause leakage). 
(4)  Check whether gas leakage occurs to the connection pipe and then apply 
thermal insulation, as shown below. 
(5)  Wind sponge around the joint of gas pipe and heat insulation sheath of gas 
collecting pipe. 
(6)  Be sure to connect gas pipe after liquid pipe is connected.