GREE U-Match 5 SERIES UNIT SERVICE MANUAL
100
Model: GUD100W/NhA-T, GUD125W/NhA-T, GUD140W/NhA-T,
GUD100W/NhA-X, GUD125W/NhA-X, GUD140W/NhA-X
Removal of electronic expansion valve
Note: Before removing the electronic expansion valve, make sure there is no refrigerant in the pipeline and power is cut off.
Step
Picture
Work instruction
1. Remove the electric box.
Remove the upper, lower and
front panels.
Loosen the wire clamp at the
bottom of the electric box
Unscrew the screws of electric
box.
The connection wires inside and
outside the electric box should be
removed.
When removing the electric box,
be careful to protect the
components.
2. Remove the fixed block.
Remove the fixed block between
the electronic expansion valve and
the pipe.
3. Remove the electronic
expansion valve.
Take off the coil of electronic
expansion valve.
Loosen the connection pipe of
electronic expansion valve by
welding. Then remove the
connection pipe.
Note: When welding the pipe, do
not let the flame bunt the other
components.