GREE         U-Match 5 SERIES UNIT SERVICE MANUAL 
78 
3.4.24 “Lp” IDU and ODU Unmatched 
Error display: ODU mainboard, IDU wired controller and IDU receiver light board will display Lp   
Error judgment condition and method: 
Possible reason: 
■Models of indoor unit and outdoor unit do not match with each other 
Troubleshooting: 
Turn off the unit and replace with a matched indoor or outdoor unit.   
3.4.25 “U7” 4–Way Valve Switch-Over Error 
Error display: ODU mainboard, IDU wired controller and IDU receiver light board will display U7   
Error judgment condition and method: 
Possible reason: 
■Voltage is abnormal. For example, low voltage will cause abnormal direction change of the 4-way valve.   
■Pilot valve holder hole or the capillary tube is blocked, which has caused small flow or no flow.   
■Capillary tube is blocked when connecting to the pilot valve or main valve.   
■Coil is not power-connected, or is open-circuited. Voltage is low, or the contact between turns or terminals is 
bad.   
■The stainless steel cover of pilot valve is damaged, or the steel core is stuck, or the spring is not elastic.   
■Insert block is bent or not elastic, so the little slide cannot get in place.   
■When adding refrigerant, the little slide is over-running and can’t spring back.   
Troubleshooting: