Cassette Type Air Conditioner Unit
30
Three-phase units (60k)
Fig. 4.43
GUHN60NM3HO+GKH60K3HI
. Power cord 5×2.5mm²(H07RN-F)
. Power cord 3×1.0mm²(H05RN-F)
. Communication Cords 2×0.75mm²(H05RN-F)
(5). Electric wiring of indoor unit side
Remove the electric box cover from the electric box sub-assy and then connect the
wire.
Fig. 4.44
CAUTION!
. The power cord and the wire of the fresh air valve are high-voltage, while the communication cord
and connection wire of the wired controller are low-voltage. They should run separately against
electromagnetic interference.
. The high-voltage and low-voltage lines should pass through the rubber rings at different electric box
covers.
. Do not bundle the connection wire of the wired controller and the communication cord together, or
arrange them in parallel, otherwise improper operation would occur.
. The high-voltage and low-voltage lines should be fixed separately and securely, with internal big
clamps for the former and small clamps for the latter.
. Tighten the indoor/outdoor connection cord and power cord respectively on the terminal boards with
screws. Faulty connection may cause a fire.
. If the indoor unit connection cord (to the outdoor unit) and power supply are wired incorrectly, the air
conditioner may be damaged.