4
Technical Information
Service Manual
The above data is subject to change without notice. Please refer to the nameplate of the unit.
Outdoor
Unit
Outdoor Unit Model GVC36ALXH-K3NTC7A/O GVH36ALXH-K3NTC7A/O
Outdoor Unit Product Code CG156W07500 CG156W07400
Compressor Manufacturer
ZHUHAI LANDA COMPRESSOR
CO.,LTD
ZHUHAI LANDA
COMPRESSOR CO.,LTD
Compressor Model QXAS-F41N470A QXAS-F41N470A
Compressor Oil
Ze-GLES RB68EP or FVC 68D or
FV 50S or equivalent
Ze-GLES RB68EP or FVC
68D or FV 50S or equivalent
Compressor Type Rotary Rotary
Compressor LRA. A 81.00 81.00
Compressor RLA A 16.00 16.00
Compressor Power Input W 3560 3560
Compressor Overload Protector / /
Throttling Method Capillary Capillary
Set Temperature Range ºC 16~30 16~30
Cooling Operation Ambient Temperature Range ºC 18~52 18~52
Heating Operation Ambient Temperature Range ºC / -7~24
Condenser Form Aluminum Fin-copper Tube Aluminum Fin-copper Tube
Condenser Pipe Diameter mm Φ7 Φ7
Condenser Rows-n Gap mm 3-1.4 3-1.4
Condenser Coil Length (LXDXW) mm 955X57.15X704 955X57.15X704
Fan Motor Speed rpm 850 850
Fan Motor Power Output W 90 90
Fan Motor RLA A 0.7 0.7
Fan Motor Capacitor μF / /
Outdoor Unit Air Flow Volume m
3
/h 4000 4000
Fan Type Axial-ow Axial-ow
Fan Diameter mm Φ570 Φ570
Defrosting Method / Automatic Defrosting
Climate Type T3 T3
Isolation I I
Moisture Protection IPX4 IPX4
Permissible Excessive Operating Pressure for
the Discharge Side
MPa 4.3 4.3
Permissible Excessive Operating Pressure for
the Suction Side
MPa 2.5 2.5
Sound Pressure Level dB (A) 62 62
Sound Power Level dB (A) 72 72
Dimension(WXHXD) mm 1000X746X427 1000X746X427
Dimension of Carton Box (LXWXH) mm 1077X480X785 1077X480X785
Dimension of Package(LXWXH) mm 1080X483X810 1080X483X810
Net Weight kg 66 68
Gross Weight kg 71 73
Refrigerant R410A R410A
Refrigerant Charge kg 2.8 2.8
Connection
Pipe
Connection Pipe Length m 5 5
Connection Pipe Gas Additional Charge g/m 50 50
Outer Diameter Liquid Pipe 3/8'' 3/8''
Outer Diameter Gas Pipe 5/8'' 5/8''
Max Distance Height m 20 20
Max Distance Length m 30 30
Note: The connection pipe applies metric diameter.