10. Malfunction of Insufcient uorine protection F0
Troubleshooting
for F0 malfunction
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Malfunction is
eliminated.
Clean the heat exchangers and
remove blockage of air inlet/outlet.
Make compressor run normally.
Remove blockage in the system
Check the leaking status of refrigerant
and charge refrigerant
Heat exchangers are
too dirty or the air inlet/outlet
is blocked.
Compressor doesn't work
normally. Strange noise or leakage
occurs.Casing is too hot.
System is blocked inside (dirt block, ice
block, oil block, Y-valve no fully open).
The refrigerant is leaking
Replace a main
board with
the same model.
End
Yes
No
No
No
No No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes