Troubleshooting
(7) Diagnosis for overload and discharge malfunction (AP1 below is control board of outdoor unit)
Main detectio
n point:
z If the electron expansion valve is connected well? Is the expansion valve damaged?
z If the refrigerant is leakage?
z If the overload protector is damaged?
Malfunction diagnosis process:
Connect wire
well with wiring
diagram
Replace EKV 
coil of electron
expansion valve
If the wiring terminal FA of electron 
expansion is well connected?
Remove
mulfunction?
The resistance value of 
first 4 lead foot and the
fifth lead foot is similar,
small to 100
ƻ
Finish
fter the unit 
de-energized 
for 20min
Remove 
mulfunction?
Y
N
N
N
If the overload protector SAT is 
well connected?
N
Under ambient temperature, test the 
resistance of  overload protector  with ohmic 
meter, resistance value  1000ƻ
Y
Y
Replace 
overload 
protector SAT
N
Y
Check refrigerant, if there is 
leakage, please refer to 
specification
Replace 
control board 
AP1