110
Installation and Maintenance
Service Manual
2.Diagnosis for anti-high temperature, overload protection (AP1 below is control board of outdoor unit)
Main detection point:
● If the outdoor ambient temperature is in normal range;
● If the indoor and outdoor fan is running normal;
● If the radiating environment of indoor and outdoor unit is well.
Malfunction diagnosis process:
 
Y
Y
Y
N
N
N
Anti-high temperature,
overload protection
If the outdoor ambient temperature is 
higher than 53 °C?
After the unit de-
energized for 20min
If the radiating of outdoor 
and indoor unit is well?
If the indoor and outdoor 
fan work well?
Replace
control board
AP1
End
Replace 
outdoorfan
Replace fan 
capacitor C1
Improve the
radiating 
environment of
unit 
Normal protection, please use 
it after improve the outdoor 
ambient temperature
1. Check if fan terminal 
OFAN is connected well
2. Test if resistance value 
of any two terminals is less 
than 1kΩ with ohmic meter