Sleep Mode 2 (Adaptive Cycle)
1. Cool or Dry Mode (Initial setpoint between 61 F. - 74 F.)
a) A er 1 hour of operation the temperature setting will raise 2 F every hour
b) A er 3 hours of operation the temperature setting will raise 6 F above initial setpoint and stay at this
setting
c) A er 7 hours of operation, the setpoint will move to 4 F. above the initial setpoint and remain until the
sleep mode in canceled.
Cool or Dry Mode (Initial setpoint between 75 F. - 81 F.)
a) A er 1 hour of operation the temperature setting will raise 2 F every hour
b) A er 3 hours of operation the temperature setting will raise 4 F above initial setpoint and stay at this
setting
c) A er 7 hours of operation, the setpoint will move to 2 F. above the initial setpoint and remain until the
sleep mode in canceled.
Cool or Dry Mode (Initial setpoint between 82 F. - 85 F.)
a) A er 1 hour of operation the temperature setting will raise 2 F every hour
b) A er 3 hours of operation the temperature setting will raise 24 F above initial setpoint and stay at this
setting
c) A er 7 hours of operation, the setpoint will move back to the initial setpoint and remain until the
sleep mode in canceled.
Cool or Dry Mode (Initial setpoint above 85 F.)
a) e original setpoint will be maintained for 7 hours, then a er 7 hours it will decrease by 1 F until the
sleep mode is canceled
2. Heat Mode (Initial setpoint 61 F.)
a) e unit will maintain this setpoint until Sleep Mode is canceled
Heat Mode (Initial setpoint between 62 F. - 68 F.)
a) A er 1 hour of operation the temperature setting will decrease 2 F and maintain this setpoint until
Sleep Mode is canceled
Heat Mode (Initial setpoint between 69 F. - 81 F.)
a) A er 1 hour of operation the temperature setting will decrease 2 F and maintain this setpoint until
Sleep Mode is canceled
Heat Mode (Initial setpoint between 82 F. - 86 F.)
a) A er 1 hour of operation the temperature setting will decrease 2 F every hour
b) A er 3 hours, the setpoint will be xed at 6 F below the initial setpoint and remain at this setpoint until
Sleep Mode is canceled