30
Installation and Maintenance
Service Manual
9. Maintenance
9.1 Error code
No. Malfunction 
Name
Display Method 
of Indoor Unit
(Error Code)
A/C Status
Possible Causes(For specic maintenance 
method, please refer to the following procedure of 
troubleshooting)
1
Indoor ambient 
temperature 
sensor is 
open/short-
circuited
F1
The unit will stop operation as it 
reaches the temperature point. 
During cooling and drying operation, 
except IDU fan motor operates, other 
loads stop operation; During heating 
operation, the system stops operation.
1.The wiring terminal between indoor ambient temperature 
sensor and main board is loosened or poorly contacted;
2.There’s short circuit due to trip-over of the parts on 
controller;
3.Indoor ambient temperature sensor is damaged (Please 
check it by referring to the resistance table for temperature 
sensor)
4. Main board is broken.
2
Indoor 
evaporator 
temperature 
sensor is 
open/short-
circuited
F2
The unit will stop operation as it 
reaches the temperature point. 
During cooling and drying operation, 
except
 IDU
 fan operates, other 
loads stop operation; During heating 
operation, the complete unit stops 
operation.
1.The wiring terminal between indoor evaporator 
temperature sensor and main board is loosened or poorly 
contacted;
2.There’s short circuit due to the trip-over of the parts on 
controller;
3.Indoor evaporator temperature sensor is damaged 
(Please check it by referring to the resistance table for 
temperature sensor)
4. Main board is broken.
3
Blocked 
protection of 
IDU fan motor
H6
IDU fan, ODU fan, compressor and 
electric heat tube stop operation. 
Horizontal louver stops at the current 
position.
1.The feedback terminal of PG motor is not connected 
tightly.
2.The control terminal of PG motor is not connected tightly.
3.Fan blade rotates unsmoothly.
4.Malfunction of motor
5.Main board is broken.
4
Malfunction 
protection of 
jumper cap
C5
Operation of remote controller or 
control panel is available, but the unit 
won’t act. 
1.There’s not jumper cap on the main board.
2.Jumper cap is not inserted properly and tightly.
3.Jumper cap is damaged.
4.Controller is damaged.
5
Overload
malfunction
E8 The entire unit stops.
1.Indoor and outdoor heat exchanger is too dirty?
Or air inlet/outlet is blocked?
2.Fan motor is not working. Abnormal fan speed; fan
speed is too low or the fan doesn't run.
3.Compressor operates normally or not? Is there any
abnormal noise or oil leak? Casing is too hot?
4.System is blocked inside? (Dirt blockage? Ice blockage?
Oil blockage? Y-valve is not fully open?)
5.Main board temperature sensor detects wrongly.