11
Technical Information
Service Manual
2.2 Capacity Curve in Different Outdoor Temperature
2.3 Cooling and Heating Data Sheet in Rated Frequency
Heating
Rated heatling condition(°C)
(DB/WB)
Model
Pressure of gas pipe connecting
indoor and outdoor unit
Inlet and outlet pipe temperature
of heat exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
20/- 7/6 18/24K 3.5~3.8
in:75~85
out:37~43
in:1~3
out:2~5
Super High High
Rated cooling condition(°C)
(DB/WB)
Model
Pressure of gas pipe connecting
indoor and outdoor unit
Inlet and outlet pipe temperature
of heat exchanger
Fan speed of
indoor unit
Fan speed of
outdoor unit
Indoor Outdoor P (MPa) T1 (°C) T2 (°C)
27/19 35/24 18/24K 0.8~1.0
in:8~11
out:11~14
in:75~85
out:37~43
Super High High
Cooling
Instruction:
T1: Inlet and outlet pipe temperature of evaporator
T2: Inlet and outlet pipe temperature of condenser
P: Pressure at the side of big valve
Connection pipe length: 5m.