106
Installation and Maintenance
Service Manual
Appendix:
1.Standard length of connection pipe
● 16.4ft,24.6ft, 26.2ft.
2.Min. length of connection pipe is 9.84ft.
3.Max. length of connection pipe and max. high difference.
4.The additional refrigerant oil and refrigerant charging required after 
prolonging connection pipe
● After the length of connection pipe is prolonged  for 32.8ft at  the 
basis of standard length, you should add 5ml of refrigerant oil for each 
additional 16.4ft of connection pipe.
● The calculation method of additional refrigerant charging amount (on 
the basis of liquid pipe):
Appendix 1: Reference Sheet of Celsius and Fahrenheit
Appendix 2: Conguration of Connection Pipe
Cooling capacity
Max length of 
connection pipe
Max height 
difference
5000 Btu/h(1465 W) 49.2 ft 16.4 ft
7000 Btu/h(2051 W) 49.2 ft 16.4 ft
9000 Btu/h(2637 W) 49.2 ft 32.8 ft
12000 Btu/h(3516 W) 65.6 ft 32.8 ft
18000 Btu/h(5274 W) 82.0 ft 32.8 ft
24000 Btu/h(7032 W) 82.0 ft 32.8 ft
28000 Btu/h(8204 W) 98.4 ft 32.8 ft
36000 Btu/h(10548 W) 98.4 ft 65.6 ft
42000 Btu/h(12306 W) 98.4 ft 65.6 ft
48000 Btu/h(14064 W) 98.4 ft 65.6 ft
Set temperature
Conversion formula for Fahrenheit degree and Celsius degree: Tf=Tcx1.8+32
Ambient temperature
 Fahrenheit 
display 
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
 Fahrenheit 
display 
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
 Fahrenheit 
display 
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
32/33 32 0 55/56 55.4 13 79/80 78.8 26
34/35 33.8 1 57/58 57.2 14 81 80.6 27
36 35.6 2 59/60 59 15 82/83 82.4 28
37/38 37.4 3 61/62 60.8 16 84/85 84.2 29
39/40 39.2 4 63 62.6 17 86/87 86 30
41/42 41 5 64/65 64.4 18 88/89 87.8 31
43/44 42.8 6 66/67 66.2 19 90 89.6 32
45 44.6 7 68/69 68 20 91/92 91.4 33
46/47 46.4 8 70/71 69.8 21 93/94 93.2 34
48/49 48.2 9 72 71.6 22 95/96 95 35
50/51 50 10 73/74 73.4 23 97/98 96.8 36
52/53 51.8 11 75/76 75.2 24 99 98.6 37
54 53.6 12 77/78 77 25
 Fahrenheit 
display 
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
 Fahrenheit 
display 
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
 Fahrenheit 
display 
temperature
(℉)
Fahrenheit
(℉)
Celsius
(℃)
61 60.8 16 69/70 69.8 21 78/79 78.8 26
62/63 62.6 17 71/72 71.6 22 80/81 80.6 27
64/65 64.4 18 73/74 73.4 23 82/83 82.4 28
66/67 66.2 19 75/76 75.2 24 84/85 84.2 29
68 68 20 77 77 25 86 86 30
● When the length  of  connection  pipe  is  above  16.4ft, add refrigerant according to the  prolonged  length  of  liquid  pipe. The 
additional refrigerant charging amount per meter is different according to the diameter of liquid pipe. See the following sheet.
● Additional refrigerant charging amount = prolonged length of liquid pipe X additional refrigerant charging amount per meter 
Additional refrigerant charging amount for R22, R407C, R410A and R134a
Diameter of connection pipe Outdoor unit throttle
Liquid pipe(inch) Gas pipe(inch) Cooling only(oz/ft) Cooling and heating(oz/ft)
Ф0.23 Ф0.37 or Ф0.47 0.53 0.71
Ф0.23 or Ф0.37 Ф0.63 or Ф0.75 0.53 0.71
Ф0.47 Ф0.75 or Ф0.84 1.06 4.23
Ф0.63 Ф1.0 or Ф1.25 2.12 4.23
Ф0.75 / 8.82 8.11
Ф0.84 / 12.34 12.34