14
A Series Inverter Modular Air-cooled Chiller (Heat Pump)
(3) Enough space shall be left for service and ventilation. There should be good ventilation around the
unit. Beside, be sure there is at least 1mbetween the unit and any barrier, and at least 1.2m should
be kept at the side of the water inlet and outlet pipes. If possible, it is better to set up a sun cover
3m ahead of the unit.
(4) The unit shall be installed where it will not be aected by re, corrosive, inammable or waste gas,
and proper measures shall be taken to minimize the vibration and noise.
(5) The unit shall be installed where the defrosting water can be drained out favorably
(6) Do not install the unit where there is heavy snow. If inevitable, build a foundation at least 300mm
higher than the ground.
■ Installation space for the single unit
(Unit
:
mm)
Outlet Outlet
Electric box
The inlet and outlet pipes
both are at this side.
Note: The unit should be installed where at least 3 sides of the unit are not blocked.
■ Installation space for modularised units
(Unit
:
mm)
Outlet Outlet Outlet Outlet