A Series Inverter Modular Air-cooled Chiller (Heat Pump)
Symptoms Probable causes Recommended action
Shutdown against low
pressure protection of
the
compressor
1. The electrostatic expansion valve is
faulty.
2. The low pressure cuto󰀨 is faulty.
3. Refrigerant is insu󰀩cient.
4. The entering chilled water
temperature is 5°C lower than the
rated.
5. The chilled water ow is too low.
1. Replace the coils or even the
valve body.
2. Check the low pressure
cuto󰀨.
3. Check and charge
refrigerant.
4. Check if the chilled water is
down-temperature.
5. Adjust the chilled water ow.
Failed startup of the
compressor
1. The overcurrent relay tripped o󰀨
and the fuse was burnt out.
2. The control circuit was open.
3. There is no current.
4. Low/high pressure protection.
5. The contact coils is burnt out.
6. The water ow is cut o󰀨.
7. The wireless controller raised the
alarm signal. ON/ OFF time setting by
the wireless controller is incorrect.
8. The sensed temperature exceeded
the rated.
1. Replace it.
2. Check wiring of the control
system.
3. Check the power supply.
4. See corresponding statement
above.
5. Replace it.
6. Check the water system.
7. Check the alarm type and
take corresponding corrective
measure.
8. Check and reset it.
Temperature sensor
protection
1. The bulb plug and the main board
plug were connected incorrectly.
2. The temperature bulb was
damaged.
3. The main board was damaged.
1. Check if the bulb plug was
connected to the correct
main board plug.
2. Replace it.
Pressure transducer
error
1. The pressure sensor is open-
circuited.
2. The pressure sensor is short-
circuited.
3. The pressure sensor is damaged.
1. Check the circuit of the
pressure sensor.
2. Replace it.
Flow switch protection
1. The water pump has not started.
2. The water ow is too low.
3. The water ow switch was
damaged.
4. There was air inside the water
system.
1. Start the water pump.
2. Adjust the water ow.
3. Adjust the water ow.
4. Dispel air inside the water
system.
Protection against the
failed 4–way valve
1. The entering and leaving water
temperature sensor fell o󰀨 or installed
incorrectly.
2. The 4–way valve was damaged.
1. Check if the entering and
leaving water temperature
sensors were installed correctly
and if silica gel at the probe for
heat conduction was applied
properly.
2. Replace it.
Protection against the
failed compressor IPM
module
1. The voltage suddenly dropped.
2. The compressor drive board was
damaged.
1. Check if it occurred before
protection.
2. Replace it.