GREE U-Match 6 SERIES UNIT SERVICE MANUAL
21
to select parameter code to P21”. Press “MODE” button to enter parameter setting. At that
time, parameter value is blinking at time displaying zone. Press “
” or “
” button to adjust
the parameter value and press “ENTER” button to finish setting. The compensation value
setting range is -15 to 15.
2) Compensation of temperature sensor in heating mode: press “
” or “
” button to select
parameter code to P22”. Press “MODE” button to enter parameter setting. At that time,
parameter value is blinking at time displaying zone. Press “
” or “
” button to adjust the
parameter value and press “ENTER” button to finish setting. The compensation value setting
range is -15 to 15.
2.3.11 Selecting fan mode of indoor fan motor
(1) Under ON or OFF status, Long press “FUNCTION” button for 5s and the temperature zone
displays “C00”; then press MODEbutton three times in one second;
(2) Long press “FUNCTION” button for another 5s to enter the interface of setting wired controller
parameters. “P00” is displayed in temperature zone;
(3) Press “
” or “
” button to select parameter code to P30”. Press “MODE” button to enter
parameter setting. At that time, parameter value is blinking at time displaying zone. Press “
” or
” button to adjust the parameter value and press “ENTER” button to finish setting. The
parameter value setting range is 01 to 09.
There are 5 selections for high external pressure (ESP) duct:
(1) P3 (LCD displays 03).
(2) P4 (LCD displays 04).
(3) P5 (LCD displays 05).
(4) P6 (LCD displays 06).
(5) P7 (LCD displays 07).
Static
pressure
selection
Super
high
speed
High
speed
Medium
high
speed
Medium
speed
Medium
low
speed
Low
speed
Quiet
R1 speed
Quiet
R2 speed
Quiet
R3 speed
P3 S09 S08 S07 S06 S05 S04 S03 S02 S01
P4 S10 S09 S08 S07 S06 S05 S04 S03 S02
P5 S11 S10 S09 S08 S07 S06 S05 S04 S03
P6 S12 S11 S10 S09 S08 S07 S06 S05 S04
P7 S13 S12 S11 S10 S09 S08 S07 S06 S05
Note:
The external static pressure (ESP) can be changed in 5 levels by the remote controller.