GREE U-Match 6 SERIES UNIT SERVICE MANUAL
22
The default ESP mode setting is P05 which is the rated ESP.
The remote controller can be used to change turbo, H, M and L.
There are 9 selections for high static pressure (ESP) duct:
(1) P1 (LCD displays 01).
(2) P2 (LCD displays 02).
(3) P3 (LCD displays 03).
(4) P4 (LCD displays 04).
(5) P5 (LCD displays 05).
(6) P6 (LCD displays 06).
(7) P7 (LCD displays 07).
(8) P8 (LCD displays 08).
(9) P9 (LCD displays 09).
Note:
You can select P01, P02, P03, P04, P05, P06, P07, P08, P09 in fan mode of indoor fan motor,
which means different fan mode combinations are corresponding to different static pressure. Ex-factory
defaulted mode is P05. You can set the mode through wired controller. S01, S02, S03……S12, S13
means the rotation speed of indoor unit is from low to high.
Combination relationship of P01, P02, P03, P04, P05, P06, P07, P08, P09.
Static
pressure
selection
Super
high
speed
High
speed
Medium
high
speed
Medium
speed
Medium
low
speed
Low
speed
Quiet
R1 speed
Quiet
R2 speed
Quiet
R3 speed
P1 S05 S03 S02 S02 S01 S01 S01 S01 S01
P2 S06 S04 S03 S03 S02 S02 S02 S02 S02
P3 S07 S05 S04 S04 S03 S03 S03 S03 S03
P4 S08 S06 S05 S05 S04 S04 S04 S04 S04
P5 S09 S07 S06 S06 S05 S05 S05 S05 S05
P6 S10 S08 S07 S07 S06 S06 S06 S06 S06
P7 S11 S09 S08 S08 S07 S07 S07 S07 S07
P8 S12 S10 S09 S09 S08 S08 S08 S08 S08
P9 S13 S11 S10 S10 S09 S09 S09 S09 S09
2.3.12 Setting of master and slave wired controller
(1) Under ON or OFF status, Long press “FUNCTION” button for 5s and the temperature zone
displays “C00”; then press MODEbutton three times in one second;
(2) Long press “FUNCTION” button for another 5s to enter the interface of setting wired controller
parameters. “P00” is displayed in temperature zone;