Operating Manual for Central Air Conditioner Thermostat
16
5.8 Modbus address setting
The Modbus monitoring system is capable
of controlling up to 255 thermostats at the same
time. Communication between the thermostat
and the Modbus monitoring system is transmitted
at 9,600bps by default. The default address is 1
and you can set the address between 1~255. You
need to set different addresses to avoid conflict
recognition.
After a stop of the unit, keep pressing for 5s to go to the Modbus
address setting page.
+
(UP) or
(DOWN) is provided to adjust the address
number. Press for 5s to save all the settings and the current page exits. The
screen goes back to the page after you stopped the unit. If there is no any key
press within 20s, the current page will exit, not saving any data you set.
5.9 Power failure memory
It can be available for turn-on and turn-o󰀨 the unit, modes, temperatures,
fan speeds, temperature units, fan operation at the set points, temperature
calibration and Modbus address. Sleep function cannot be memorised but a
change to the communication baud rate can.