MICROGUARD RCI 510 TROUBLESHOOTING MANUAL 5 W450260D 03/10
2.3 FAULT REPORTING AND FAULT CODES
SYSTEM FAULT CODES provide one of the most important ways to quickly locate and assess problems
in the MicroGuard®System. Please review this section carefully.
Each time the system is turned on, it goes through a self-testing process lasting six seconds that
automatically detects most faults in the system. During normal operation, a self-test can be initiated
at any time by pressing the TEST button on the display console.
Many fault conditions are detected without a system self-test.
Faults detected in the system during the self-test, are indicated on the display console in the
following ways:
The RED OVERLOAD LAMP will illuminate.
The AUDIBLE ALARM will sound.
WARNING SYSTEM FAULT!” will be displayed at the bottom of the text window.
Fault codes may be displayed on the display console. To view the codes, press and hold the TEST
button and wait for the system to complete the self-test. Do not release the TEST button. Fault codes
will now be displayed at the bottom of the text window for as long as the TEST button is held down.
FAULTS A000 B0 C00 D00
FIGURE 2.3
FAULT CODE DISPLAY SHOWN IN LOWER PORTION OF TEXT DISPLAY WINDOW
There are four groups of FAULT CODES: A,B,C & D. The function of these groups and a complete listing
of each code is provided on the following pages.
NOTE: ALWAYS INVESTIGATE FAULTS IN THE “B” AND “C” GROUPS BEFORE CONTINUING
WITH A AND FINALLY “D GROUP FAULTS.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GREER Company MicroGuard RCI 510 and is the answer not in the manual?

GREER Company MicroGuard RCI 510 Specifications

General IconGeneral
BrandGREER Company
ModelMicroGuard RCI 510
CategoryIndustrial Equipment
LanguageEnglish