Terminal Function
91 (L1)
Three-phase mains supply92 (L2)
93 (L3)
95/99 (PE) Protective earth connection
96 (U)
Three-phase motor connection, 0-100 % of mains
voltage
97 (V)
98 (W)
For single-phase connection, use L1
and L2.
Mains connection
1. Connect the earth conductor to terminal 95 (PE).
2. Connect the mains conductors to terminals 91 (L1), 92 (L2), 93
(L3).
3. Fix the mains cable with a cable clamp.
See Appendix.
Motor connection, enclosures
1. Connect the earth conductor to terminal 99 (PE).
2. Connect the motor conductors to terminals 96 (U), 97 (V), 98
(W) of the motor plug.
3. Fix the screened cable with a cable clamp.
Enclosure
Torque Nm [ft (lb)]
Mains Motor
Protective
earth
Relay
A2 1.8 (1.3) 1.8 (1.3) 3 (2.2) 0.6 (0.4)
A3 1.8 (1.3) 1.8 (1.3) 3 (2.2) 0.6 (0.4)
A4 1.8 (1.3) 1.8 (1.3) 3 (2.2) 0.6 (0.4)
A5 1.8 (1.3) 1.8 (1.3) 3 (2.2) 0.6 (0.4)
B1 1.8 (1.3) 1.8 (1.3) 3 (2.2) 0.6 (0.4)
B2 4.5 (3.3) 4.5 (3.3) 3 (2.2) 0.6 (0.4)
B3 1.8 (1.3) 1.8 (1.3) 3 (2.2) 0.6 (0.4)
B4 4.5 (3.3) 4.5 (3.3) 3 (2.2) 0.6 (0.4)
C1 10 (7.4) 10 (7.4) 3 (2.2) 0.6 (0.4)
C2
14
1
/24
2
(10.3
1
/
17.7
2
)
14
1
/24
2
(10.3
1
/
17.7
2
)
3 (2.2) 0.6 (0.4)
C3 10 10 3 (2.2) 0.6 (0.4)
C4
14
1
/24
2
(10.3
1
/
17.7
2
)
14
1
/24
2
(10.3
1
/
17.7
2
)
3 (2.2) 0.6 (0.4)
D1h 19-40 19-40 3 (2.2) 0.6 (0.4)
D2h 19-40 19-40 3 (2.2) 0.6 (0.4)
1
Conductor cross-section ≤ 95 mm
2
(≤ 4/0 AWG)
2
Conductor cross-section ≥ 95 mm
2
(≥ 4/0 AWG).
STO installation, optional
DANGER
Exposure to high pressure or toxic
liquids
Death or serious personal injury
Failure to remove the
jumper disables the STO
function, and the motor might not
stop as intended, and can cause
severe injury or death.
Failure to use safety-monitoring
relay compliant with Category 3/
PL d according to ISO 13849-1 or
SIL 2 according to EN 62061 and
IEC 61508 can cause death or
serious personal injury. Perform a
functional test every 12 months to
ensure that the system works
properly.
12
37
1
3
FC
4
2
TM074594
STO wiring
Pos. Description
1 Reset button
2 Safety relay (category 3, PL d or SIL2)
3 Emergency stop button
4
Short-circuit protected cable if the product is not
installed inside an IP54 cabinet.
Connecting the signal terminals
As a precaution, signal cables must be
separated from other cable groups by
reinforced insulation in their entire
lengths.
Connect the signal cables according to the guidelines for good
practice to ensure EMC-correct installation.
Use screened signal cables with a cable cross-section of
minimum 0.5 mm
2
and maximum 1.5 mm
2
.
Use a 3-conductor screened bus cable in new systems.
Connection of a thermistor (PTC) to CUE
A PELV circuit provides protection against electric shock. Special
connection requirements apply to this type of circuit. The
requirements are described in EN 61800-5-1.
9
English (GB)