11.4 OUTPUTS
The unit provides 2 relay and 4 semiconductor outputs. 2 of them have programmable funcons, selectable
from a list. Any funcon or alarm condion may be a digital output. Using two Relay Expansion Modules, the
number of relays may be increased to 22, 16 of them being volt-free contacts.
11.5 EVENT LOGGING
The unit records last 100 events with date-me stamp and a total of 18 measured parameters.
11.5 TELEMETRY AND REMOTE PROGRAMMING
The unit provides the user with large telemetry facilies via its standard RS-232 serial port, connecng either
to a PC, PLC or a GSM or PSTN modem. It supports both RAINBOW and MODBUS communicaon protocols.
The standard PC soware oers local and modem operaon capabilies as well as modem networking feature.
The PC program is used for below purposes:
parameter upload/download
remote monitoring and control
diagnoscs and analysis
Alternator voltage: 0 to 300 V-AC (Ph-N)
Alternator frequency: 0-100 Hz.
Mains voltage: 0 to 300 V-AC (Ph-N)
Mains frequency: 0-100 Hz.
V-A-cos Accuracy: 1.0% + 1 digit
kW-kVA-kVAr Accuracy: 2.0% + 1 digit
DC Supply Range: 9.0 to 33.0 V-DC
Cranking dropouts: survives 0 V for 100ms.
Typical Standby Current: 100 mA-DC
Maximum Operang Current: 200 mA-DC (Relay
outputs open)
Generator/Mains Contactor Relay Outputs: 16 A /
250V
DC Outputs: 1A @ 28V protected semiconductor
output
Charge excitaon: min 2 Was
Magnec pickup input:: 0.5 – 30 V-AC.
Magnec pickup frequency: 10 KHz max.
Current inputs: from CTs, .../5A. Max load 0.7VA
per phase.
Analog input range: 0-5000 ohms.
Serial port: RS-232, 9600 bauds, no parity, 1 bit stop
Operang temp.: -20
O
C (-4
O
F) to 70
O
C (158
O
F).
Storage temp.: -40
O
C (-40
O
F) to 80
O
C (176
O
F).
Maximum humidity: 95% non-condensing.
Dimensions: 172 x 134 x 46 mm (WxHxD)
Panel Cut-out Dimensions: 151x111 mm mini-
mum.
Weight: 340 g (approx.)
Case Material: High Temperature ABS/PC
(UL94-V0)
IP Protecon: IP65 from front panel, IP30 from
the rear
Installaon: Flat surface mounng on a Type 1
Enclosure. Rear retaining plasc brackets.
CE Conformity reference standards:
EN 61010 (safety requirements)
EN 61326 (EMC requirements)
UL / CSA Conformity: cercate # 20110527-
E314374
UL 508, Edion 17
UL 2200, 1st Edion.
UL 840 Edion 3
CSA C22.2 NO. 14 - Edion 10
11.5.1 TECHNICAL SPECIFICATIONS
Oil Pressure Sender
Coolant Temp. Sender
FUSE
FUSE
FUSE
Mains
Contactor
Generator
Contactor
MS
TETO
FUSE
Electricalnterloc
emoteMonitorin