Outdoor Unit
231
Super Match
Item Model 1U60IS2ERB(S)
Power cable H07RN-F 5G 4.0mm2
Communication cable /
Connecting cable H05RN-F 4G 1.5mm2
Power source(outdoor unit) N, V, Hz 3N~,380~400V, 50Hz
Start Current A 5
Outdoor unit
Unit model (color) 1U60IS2ERB(S)(WHITE)
Compressor
Model / Manufacture/place
TNB306FPNMC(MITSUBISHI ELECTRIC
COMPRESSOR CO.,LTD)
OIL model FV50S
Oil charging 870CM3
Type Twin Rotary/1
Fan
Type × Number axial×2
Speed r/min 860±30/750±40/620±40
Fan motor input power kW 0.145×2
Fan motor output power kW 0.075×2
Air-ow(H-M-L) m³/h 6000
Heat
exchanger
Type / Diameter mm TP2M/Φ7.94
Row/Fin pitch 2 1.5
Total area m² 1.17
Dimension
External
(
L×W×H
)
mm×mm×mm 948×340×1250
Package
(
L×W×H
)
mm×mm×mm 1095×410×1400
Drainage pipe (material , I.D./O.D.) mm /
Refrigerant control method mm/mm Electronic Expansion Valve 2.4MM
Defrosting auto
Volume of Accumulator L 4.0
Sound power Noise level (H-M-L) dB(A) 73
Sound pressure Noise level (H-M-L) dB(A) 60
Type of Four way valve SHF-20D-46
material of reduce noise XPE
crankcase heater power W 38
Weight(Net / Shipping) kg / kg 93/103
PIPING
Refrigerant
Type / Charge g R410A/3300
Maximum pipe length without
recharge refrigerant
m 20
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Connecting Method ared
Between I.D
&O.D
MAX.Drop m 30
MAX.Piping length m 50
Working temp
` ºC 10
~
46
Heatling (Min-Max) ºC -15
~
24
Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating): 20
℃
DB
Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating): 7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound
intensity meter. It is a sound pressure noise level.