2. Indoor unit dip switch setting and function
AD24MS1ERA AD28/36/48NS1ERA(S) AD48/60HS1ERA(S) AB09/12/18CS1ERA(S) AB24/28/36/48ES1ERA(S)
AB60CS1ERA(S) AB60ES2ERA(S) AP48/60KS1ERA(S) AC12/18/24CS1ERA(S) AC28/36ES1ERA(S)
AC48/60FS1ERA(S) AD09LS1ERA AD12LS1ERA AD18LS1ERA AD24LS1ERA AD24MS1ERA(D)
(1: ON 0: OFF)
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
1 0 0 --- --- --- --- --- 09K indoor unit
0 1 0 --- --- --- --- --- 12K indoor unit
0 0 1 --- --- --- --- --- 18K indoor unit
1 0 1 --- --- --- --- --- 24K indoor unit
0 1 1 --- --- --- --- --- 28K indoor unit
1 1 1 --- --- --- --- --- 36K indoor unit
1 1 0 --- --- --- --- --- 48K indoor unit
1 1 0 --- --- --- --- --- 60K indoor unit
--- --- --- 0 --- --- --- --- Room card unavailable(default)
--- --- --- 1 --- --- --- --- Room card available
--- --- --- --- 0 --- --- --- heat pump(default)
--- --- --- --- 1 --- --- --- cooling only
--- --- --- --- --- 0 --- ---
Tempetature compensation unavailable
(Duct/Cabient type are default)
--- --- --- --- --- 1 --- ---
Tempetature compensation
available(Cassette/Convertible type are
default)
--- --- --- --- --- --- 0 0 Cassette
--- --- --- --- --- --- 0 1 Cabinet
--- --- --- --- --- --- 1 0 Duct
--- --- --- --- --- --- 1 1 Convertible
AD09~24SS1ERA AD09~24SS1ERA(N)(P) AD09~24SS1ERA(N) AD12MS1ERA AD18MS1ERA
AD12MS1ERA(D) AD18MS1ERA(D) AD24MS2ERA AD24MS2ERA(D)
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
1 0 0 --- --- --- --- --- 09K indoor unit
0 1 0 --- --- --- --- --- 12K indoor unit
0 0 1 --- --- --- --- --- 18K indoor unit
1 0 1 --- --- --- --- --- 24K indoor unit
0 1 1 --- --- --- --- --- 28K indoor unit
--- --- --- 0 0 --- --- --- Static pressure: 1st
--- --- --- 0 1 --- --- --- Static pressure: 2nd
--- --- --- 1 0 --- --- --- Static pressure: 3rd
--- --- --- 1 1 --- --- --- Static pressure: 4th
--- --- --- --- --- 1 --- --- Room card available
--- --- --- --- --- 0 --- --- Room card unavailable(default)
--- --- --- --- --- --- 1 1 Slim duct
AD**SS1ERA)
--- --- --- --- --- --- 1 0 Med ESP duct(AD*NS orAD*MS)