26
Super Match
Item Model AB60CS1ERA(S)/1U60IS1EAB(S)
Function cooling heating
Capacity kW 15.1 16.3
Sensible heat ratio 0.73
Total power input kW 5.01 5.07
Max. power input W 6500 6500
EER or COP W/W 3.01(B) 3.21(C)
Dehumidifying capacity 10
‐
³×m³/h 5.5
Power cable /
Power source N, V, Hz 1, 220
~
230, 50
Running /Max.Running current A / A 8.6/10.5 8.6/10.5
Start Current A /
Indoor
unit
Unit model (color) AB60CS1ERA(S)
Fan
Type × Number CENTRIFUGALX1
Speed(H-M-L) r/min 630/550/440±50
Fan motor input power kW 0.19
Fan motor output power kW 0.06
Air-ow(H-M-L) m³/h 1980/1750/1500
Heat exchanger
Type / Diameter mm inner grooved pipe/φ7.0
Row 2
Total area m² 0.576
Dimension
External
(
L×W×H
)
mm×mm×mm 1230×840×280
Package
(
L×W×H
)
mm×mm×mm 1325×920×370
Drainage pipe (material , I.D./O.D.) mm PVC 26/32
Controller (O-Optional,S-Standard)
Wired YR-E17(O) YR-E16A(O)
Infrared YR-HD(S)
Fresh air hole dimension mm /
Electricity heater kW 0
Noise level (H-M-L) dB(A) 50/45/42
Weight (Net / Shipping) kg / kg 46/53
Panel
Model PB-1340IB
External dimensions(W/D/H) mm 1340/950/80
Shipping dimensions(W/D/H) mm 1400/995/115
Net weight/Shipping weight kg 8.4/12.0
Piping
Refrigerant
Type / Charge g R410A/3300
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 19.05
Between I.D
&O.D
MAX.Drop m 30
MAX.Piping length m 50
Norminal condition: indoor temperature (cooling): 27
℃
DB/19
℃
WB, indoor temperature (heating): 20
℃
DB
Outdoor temperature(cooling): 35
℃
DB/24
℃
WB, outdoor temperature(heating): 7
℃
DB/6
℃
WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter. It
is a sound pressure noise level.