Super Match
Installation Manual For Wire Controller
There are three methods to connection wire controller and the indoor units:
A.One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the
wire controller and the master unit (the indoor unit connected with wire controller directly), the others connect with
the master unit through 2 pieces of polar wire.
B. One wire controller controls one indoor unit, and the indoor unit connects with the wire controller through 3
pieces of polar wire.
C. Two wired controllers control one indoor unit. The wire controller connected with indoor unit is called master
one, the other is called slave one. Master wire controller and indoor unit; master and slave wire controllers are all
connected through 3 pieces of polar wire.
6. Communication wiring:
The wire controller is equipped with special communication wiring in the accessories. 3-core terminal (1-white
2-yellow 3-red) is connected with the terminal A, B, C of wire controller respectively.
The communication wiring is 5 meter long; if the actual length is more than it, please distribute wiring according to
below table:
*One side of the shielded sheet of communication wire must be earthed.
Communication wiring length(m) Dimensions of wiring
100 0.3mm
2
x3-core shielded wire
100 and <200 0.5mm
2
x3-core shielded wire
200 and <300 0.75mm
2
x3-core shielded wire
300 and <400 1.25mm
2
x3-core shielded wire
400 and <600 2mm
2
x3-core shielded wire
TYPE 2: For other indoor units.