48
Super Match
R0.4 ~ 0.8
Pipe size Tighten torque A(mm) Flare shape
6.35
1420~1720N.cm
(144~176kgf.cm)
8.3~8.7
9.52
3270~3990N.cm
(333~407kgf.cm)
12.0~12.4
12.7
4950~6030N.cm
(490~500kgf.cm)
12.4~16.6
15.88
6180~7540N.cm
(630~770kgf.cm)
18.6~19.0
19.05
9720~11860 N.cm
(990~1210 kgf.cm)
22.9~23.3
6. INSTALLATION OF WATER DRAINAGE PIPE
(1) Install water drainage pipe
■ Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm).
■ Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.
■ If downward slope can't be made, take other measures to lift it up.
■ Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
■ Use the self-provided stiff pipe and clamp 1 with unit. Insert water pipe into water plug until it reaches the white
tape. Tighten the clip until head of the screw is less than 4mm from hose.
■ Wind the drain hose to the clip using seal pad 9.
■ Insulate drain hose in the room.