48
Super Match
R0.4 ~ 0.8
Pipe size Tighten torque A(mm) Flare shape
6.35
1420~1720N.cm
(144~176kgf.cm)
8.3~8.7
9.52
3270~3990N.cm
(333~407kgf.cm)
12.0~12.4
12.7
4950~6030N.cm
(490~500kgf.cm)
12.4~16.6
15.88
6180~7540N.cm
(630~770kgf.cm)
18.6~19.0
19.05
9720~11860 N.cm
(990~1210 kgf.cm)
22.9~23.3
6. INSTALLATION OF WATER DRAINAGE PIPE
(1) Install water drainage pipe
Pipe dia, shall be equal or larger than that of unit piping.(pipe of polyethylent; size: 25mm; O.D:32mm).
Drain pipe should be short, with a downward slope at least 1/100 to prevent air bag from happening.
If downward slope can't be made, take other measures to lift it up.
Keep a distance of 1-1.5m between suspending brackets, to make water hose straight.
Use the self-provided stiff pipe and clamp 1 with unit. Insert water pipe into water plug until it reaches the white
tape. Tighten the clip until head of the screw is less than 4mm from hose.
Wind the drain hose to the clip using seal pad 9.
Insulate drain hose in the room.