244
4)Outdoor valves’ spare parts control
SW9 SW10 SW11 Function Operation
6 0 2 Manual control 4WV switch
Display current state of spare parts, 1: On, 0: Off
Press SW2(UP) for 2 secs continuously, displaying 1111 then come
into the setting state with blinking display: press SW2(UP) to open;
press SW1(DOWN) to close; exit the setting state automatically after
2 mins.
Press SW1(DOWN) for 2 secs continuously, displaying 0000 to exit
the setting state and stop blinking.
(Compressor is forbidden to start up when there are system failures)
6 1 2 Manual control SV1 switch
6 2 2 Manual control SV3i switch
6 3 2 Manual control SV31switch
6 4 2 Manual control SV6 switch
6 5 2 Manual control SV9 switch
6 6 2 Control SV10 switch
6 7 2 Manual control SV11 switch
6 8 2 Manual control SV18i switch
6 9 2 Manual control SV181 switch
6 10 2 Manual control SV21 switch
6 11 2
Manual control fixed frequency
compressor COMP1 switch
6 12 2
Manual control fixed frequency
compressor COMP2 switch
6 13 2 Manual control CHi switch
6 14 2 Manual control 4WV2 switch
6 15 2
Cancel all the manual control
spare parts
Press SW2(UP) for 2 secs continuously, displaying 1111 to cancel or
press SW1(DOWN) for 2 secs continuously, displaying 0000 to cancel
Cancelled items:
The manual control of compressor, fan motor, EEV LEV, Solenoid
valve and all the other outdoor active spare parts.(including air
evacuating and charging setting; excluding running modes: rated or
forced ON/OFF of indoors and outdoors, etc)
5) Phase detect parameter
SW9 SW10 SW11 Function Operation
11 0 0
OK times of S phase
20 times: normal; less than 16 times
alarm 37-1)
11 1-10 0 Observe S phase low level’s time 10ms; unit:0.1ms
11 0 1
OK times of S phase
20 times: normal; less than 16 times
alarm 37-1)
11 1-10 1
OK times of S phase
20 times: normal; less than 16 times
alarm 37-1)
11 0 2
OK times of T phase
20 times: normal; less than 16 times
alarm 37-2)
11 1-10 2 Observe T phase low level’s time 10ms; unit:0.1ms
11 0 3
OK times of T phase
20 times: normal; less than 16 times
alarm 37-2)
11 1-10 3
0.1ms
Observe T phase’s cyclic period 20ms. Unit: 0.1ms
11 0 4
OK times of S/T phase
10 times: normal; less than 7 times
alarm 37-3)