69
Item Model AD140S2SM3FA/1UH140P1ERG
Function Cooling Heating
Capacity kW 13.4(3.5~15.0) 15.5(4~19.0)
Sensible heat ratio 0.74
Total power input kW 4.05(1.0-6.5) 4.18(1.0-6.5)
Max. power input W 6500 6500
EER or COP W/W 3.31(A) 3.70(A)
Dehumidifying capacity 10
-3
×m
3
/h 4.9
Power cable /
Power source N, V, Hz 1PH, 220-240V~, 50/60Hz
Running/Max. Running current A/A
18.0(8.7-30.0)/32A 18.5(8.7-30.0)/32A
Start current A /
Circuit breaker A
Indoor unit
Unit model (color) AD140S2SM3FA
Fan
Type×Number CENTRIFUGALX3
Speed (H-M-L) r/min 1180/1080/990/930
Fan motor output/ input power kW 0.285
Air-ow (H-M-L) kW 0.200
External static pressure m
3
/h
2500/2160/1780/1500(25/37(default)/
50/70/90/100/110/120/130/150Pa)
Heat
exchanger
Type/Diameter mm Inner grooved pipe/φ7.0
Total area m
2
/
Dimension
External (L×W×H) mm×mm×mm 1500*700*248
Package (L×W×H) mm×mm×mm 1710/870/330
Drainage pipe (material, I.D./O.D.) mm PVC 21/25
Controller (O-Optional, S-Standard)
Wired YR-E17(S)
Infrared YR-HBS01(O)
Fresh air hole dimension mm 123
Electricity heater kW 0
Sound power noise level (H-M-L) dB (A) 66
Sound pressure noise level (H-M-L) dB (A) 46/43/38
Weight (Net / Shipping) kg / kg 52/62
Piping
Refrigerant
Type / Charge
g
R410A/3700
Recharge quantity
g/m
45
Pipe
Liquid
mm
9.52
Gas
mm
15.88
Between I.D
&O.D
MAX.Drop
m
30
MAX.Piping length
m
75
Norminal condition:
Indoor temperature (cooling): 27°C DB/19°C WB, indoor temperature (heating): 20°C DB
Outdoor temperature (cooling): 35°C DB/24°C WB, outdoor temperature (heating): 7°C DB/6°C WB
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity
meter. It is a sound pressure noise level.