This document is the Operation and Installation Manual for the Haier DUCT TYPE AIR CONDITIONER, specifically model AD160S2SM3FA. It provides comprehensive information for both users and professional installers to ensure safe and efficient operation and maintenance of the unit.
Function Description:
The Haier DUCT TYPE AIR CONDITIONER is designed for cooling and heating indoor spaces. It operates as a partial unit air conditioner, meaning it must be connected to a compatible outdoor unit. The system utilizes a heat pump for warming, concentrating heat from outdoor air to warm the indoor space. It features a "HOT KEEP" function to prevent cold drafts during heating startup and defrosting operations. The unit is designed for installation in various environments, including offices, restaurants, and residences, but specific precautions are outlined for industrial or challenging settings.
Important Technical Specifications:
- Model: AD160S2SM3FA
- Refrigerant: R32 (or R410A, depending on the outdoor unit). The appliance is filled with R32.
- Maximum Working Pressure: 4.3 MPa
- A-weighted Sound Pressure Level: Below 70 dB
- Applicable Ambient Temperature Range:
- Cooling:
- Indoor: max. 32/23°C DB/WB, min. 18/14°C DB/WB
- Outdoor: max. 46/26°C DB/WB, min. 10/6°C DB/WB
- Heating:
- Indoor: max. 27°C DB/WB, min. 15°C DB/WB
- Outdoor: max. 24/18°C DB/WB, min. -15°C DB/WB
- Minimum Floor Area for Indoor Unit Installation: 2 m²
- Maximum Refrigerant Charge Amount: 1.7 kg
- Indoor Unit Installation Height: At least 2.5m
- Power Cable Specifications:
- H05RN-F 3G 4.0mm² (for outdoor unit 1UH071/105N1ERG)
- H05RN-F 3G 6.0mm² (for outdoor unit 1UH125/140P1ERG)
- H05RN-F 5G 4.0mm² (for outdoor unit 1UH125/140P1EK/1U160S2SP1FB)
- Connecting Cable Specification: H05RN-F 4G 2.5mm²
- Circuit Breaker (for AD160S2SM3FA):
- Switch Breaker: 40A
- Overcurrent Protector Rated Capacity: 30A
- Power Source Wire Size (minimum): 6.0mm²
- Earth Leakage Breaker Switch: 40A
- Earth Leakage Breaker Leak Current: 30mA
- Fuse on Indoor PC Board: T 3.15A/250V
- Pipe Size (AD160S2SM3FA):
- Liquid side: Ø9.52mm
- Gas side: Ø19.05mm
- Drain Opening Size: Ø25mm
- Static Pressure Grades: 10 different ESP settings (25 Pa to 150 Pa), adjustable via wired controller YR-E17 or Infrared remote controller RE-02 (or YR-HBS01).
- Dimensions for Installation (AD160S2SM3FA):
- A (Hanging bolt position): 1562mm
- B (Ceiling hole size): 2012mm
- C (Panel dimensions): 2072mm
- D (Hanging bolt position): 620mm
- E (Ceiling hole size): 765mm
- F (Panel dimensions): 825mm
- Combination with silent panel: 366mm
Usage Features:
- Wired Controller (YR-E17): Allows for control of up to 16 indoor units. Supports static pressure grade adjustment.
- Infrared Remote Controller (RE-02 or YR-HBS01): Provides remote control functionality and static pressure adjustment.
- Heating Mode ("HOT KEEP"): Prevents cold air discharge during startup and defrost cycles, ensuring user comfort.
- Defrosting Operation: Automatic defrosting occurs approximately every hour for 5-12 minutes when frost accumulates on the outdoor unit's heat exchanger, interrupting heating.
- Room Thermostat Actuation: Fan speed adjusts automatically based on room temperature to optimize heating.
- Duct Type Design: Allows for flexible air distribution through ducts, with standard specifications for 2-spot, 3-spot, and 4-spot ducts.
- Fresh Air Inlet: Can be configured from the side or rear faces depending on working conditions.
Maintenance Features:
- Air Filter Cleaning: Filters can be cleaned by tapping, vacuuming, or washing with lukewarm water and neutral detergent.
- Unit Cleaning: The unit's exterior can be cleaned with a soft, dry cloth or a damp cloth with neutral detergent.
- Post-Season Care: Recommended to operate the unit in FAN mode for half a day to dry the interior, then turn off the power supply, and clean the air filter.
- Pre-Season Care: Check for obstructions at air inlet/outlet, ensure clean air filter, and turn on power 12 hours before starting operation.
- Professional Servicing: Regular inspection and maintenance by qualified personnel are recommended every three years to prevent capacity decrease due to contamination.
- Troubleshooting Guide: The manual includes a detailed troubleshooting section with common issues, their causes, and solutions, as well as an LED flash code table for indoor unit malfunctions.
- Refrigerant Handling: Strict guidelines for handling, installation, cleaning, servicing, and disposal of refrigerant are provided, emphasizing the need for qualified personnel and adherence to national gas regulations.
- Disposal Information: Detailed instructions for the environmentally responsible disposal of the old air conditioner and its packaging materials are included, aligning with European regulations (WEEE, RoHS).