5.2.5.. Electrical Control Functions For Cassette and Convertible type
1. Dip switch functions:
A
>_]]VbTZR\ <Zb >_^UZdZ_^Vb
-89-
AB*CS1ERA, AC*CS1ERA, AD*LS1ERA: SW1-1~~SW1-8
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8 Description
ONOFFOFF*****09 indoor
OFFONOFF*****12 indoor
OFFOFFON*****18 indoor
ONOFFON*****24 indoor
* **OFF****Room card invalid
* **ON****Room card valid
* * * * OFF * * * Heat pump
* ***ON***Cooling only
* ****OFF**Without temperature compensation
* ****ON**with temperature compensation
* *****OFFOFFCassette
* *****OFFON2P Convertible
* *****ONOFFDuct
* *****ONON5P Convertible
wiring controller address SW2-1 SW2-2 SW2-3 SW2-4
master unit OFF OFF OFF OFF
slave unit 1 ON OFF OFF OFF
slave unit 2 OFF ON OFF OFF
slave unit 3 ON ON OFF OFF
………… ………… ………… ………… …………
slave unit 15 ON ON ON ON
SW2: wiring controller communication address
when the wiring controller is used to control many units , the wiring controller communication
address of indoor unit need be setted