2)  The wire control organ displays the alarm signal with “E0” 
“E0” means the floater switch of indoor unit is abnormal  
replacing the switch
if the function of the 
floater is normal
if the floater swith is 
orientated correctly
the alarm signal of wire 
control organ is E0
begining
amend the oritation of 
the floater switch 
N
Y
N
 
Figure 7-4 
 
3)  The wire control organ displays the alarm signal with “E1” 
“E1” means indoor ambient temperature sensor is abnormal   
amend the 
position of the 
sensor
if the indoor ambient sensor 
is orientated correctly
replacing the sensor
N
if the resistance of 
sensor is right
Y
N
wire control organ displays 
the alarm signal with E1
begining
 
Figure 7-5 
 
Notation: The resistance of indoor ambient sensor is 23K 
-53-