163
Smart Power
BM1 (1-ON, 0-OFF)
Capacity (SW1-1→SW1-3)
Room
card
SW1-4
Running mode Unit Type
SW1-1 SW1-2 SW1-3 SW1-5 SW1-6 SW1-7 SW1-8 Description
ON OFF ON --- --- --- --- --- ADH105H1ERG
OFF ON ON --- --- --- --- --- ADH125H1ERG
ON ON ON --- --- --- --- --- ADH140H1ERG
ON ON OFF --- --- --- --- --- ADH160H1ERG
--- --- --- OFF --- --- --- --- Room card invaild(default)
--- --- --- ON --- --- --- --- Room card valid
--- --- --- --- OFF --- --- --- Heat pump (default)
--- --- --- --- ON --- --- --- Cooling only
--- --- --- --- --- OFF Fresh air function
--- --- --- --- --- ON Trouble alarm
--- --- --- --- --- --- OFF Without lter reminding(default)
--- --- --- --- --- --- ON With lter reminding
--- --- --- --- --- --- --- OFF Reseved
ADH105H1ERG ADH125H1ERG ADH140H1ERG ADH160H1ERG PCB code 0151800227B
SW3-5 SW3-6 SW3-7 SW3-8
Indoor unit Address
(Indoor unit address for one wired
controller control more than one
unit)
0 0 0 0 0 (master)
0 0 0 1 1(slave)
0 0 1 0 2(slave)
0 0 1 1 3(slave)
0 1 0 0 4(slave)
0 1 0 1 5(slave)
0 1 1 0 6(slave)
0 1 1 1 7(slave)
1 0 0 0 8(slave)
1 0 0 1 9(slave)
1 0 1 0 10(slave)
1 0 1 1 11(slave)
1 1 0 0 12(slave)
1 1 0 1 13(slave)
1 1 1 0 14(slave)
1 1 1 1 15(slave)
Wired controller communication address
Dip switch setting for SW3_1 SW3_1 SW3_2 SW3_4 is OFF, and the they are reserved.