175
Smart Power
ADH071M1ERG ADH090M1ERG ADH105M1ERG ADH125M1ERG ADH140M1ERG
LED ash times of
indoor PCB
Wired
controller
display
Contents of Possible reasons
LED4 LED3
0 1 01
Malfunction of indoor unit ambient
temperature sensor
Sensor disconected, or broken, or at
wrong position, or short circuit
0 2 02
Malfunction of indoor unit piping
temperature sensor
Sensor disconected, or briken, or at
wrong position, or short circuit
0 4 04 EEPROM wrong of indoor PCB
EEPROM chip disconected or broken
or wrong program-med, or PCB broken
0 7 07
Abnormal communication between
indoor and outdoor units
Wrong connection,or the wires be
disconected or wrong adress setting
of indoor unit or faulty power supply or
PCB hardware malfunction
0 8 08
Abnormal communication between
wired controller and indoor unit
Wrong connection or wired controller
broken, or PCB hardware malfunction
0 12 0C Malfunction of drain system
Pump motor disconnected or at
wrong position, or the oat switch,
disconnected, or at wrong position, or
the short circuit bridge disconne ted
0 13 0D Zero cross sigal wrong Zero cross sigal detected wrong
0 14 0E
Abnormal communication between
main control PCB & fan motor drive
Communication wire disconected or
wrong conected or PCB hardware
malfunction
0 15 0F Fan motor overcurrent Fan motor current too high
0 17 11 DC voltage high or low
DC voltage of the fan motor driver too
high or too low
0 18 12 F.M.D temperature high Fan motor driver over 95°C
0 19 13 Fan motor out of step Wrong rotor location detected
M (≥1) N (≥0) / Error of the outdoor unit See note 1,2
Note:
1. The outdoor failure can also be indicated by the indoor unit,the checking method as follows:outdoor unit error
code=(M*10+N)-20.LED4 ash M times and LED3 ash N times .
2. LED4 is a yellow one on the indoor main control PCB,LED3 is a green one.
3. To get much more details about the out door unit failure,please refer to the outdoor unit trouble shooting list.