Loading...
191
Smart Power
1. Compressor type MNB42FFDMC-L:
No. Error description
Device
protection
value
1 Compressor phase current Limit frequency protection shutdown current value (RMS) 19.1A
2 Compressor phase current Limit frequency protection decrease frequency current value (RMS) 18.4A
3 Compressor phase current Limit frequency protection recovery current value (RMS) 17.7A
4 PIM temperature shutdown protection 105°C
5 DC bus overvoltage shutdown value 700V
6 DC bus overvoltage recovery value 650V
7 DC bus under voltage shutdown value 370V
8 DC bus under voltage recovery value 430V
9 Communication shutdown protection time 30S