194
Smart Power
DC bus over/under voltage protection
Bus voltage>overvoltage shutdown value, the compressor stop, then drive into the bus overvoltage protection.
Bus voltage<overvoltage recovery value, cancel the bus overvoltage protection.
Bus voltage<under voltage shutdown value, the compressor stop, then drive into the bus under voltage protection.
Bus voltage>voltage recovery value, cancel the bus under voltage protection.
AC input over/under voltage protection
Drive come with AC voltage detection, avoid the input voltage is too low, cause the input current is too high,
damage the device.
Input voltage<under voltage shutdown value, the compressor stop, then drive into the input under voltage
protection.
Input voltage>voltage recovery value, cancel the under voltage protection.
Drive come with AC voltage detection, avoid the input voltage is too high, damage the device.
Input voltage>overvoltage shutdown value, the compressor stop, then drive into the input overvoltage protection.
Input voltage<overvoltage recovery value, cancel input overvoltage protection.
Communication error
If model code is our of model range or no right communication data is received within 30s, communication failure is
conrmed, execute stop protection under communication failure, in the meanwhile, relevant error code is sent back.
When communication is conrmed, if right data is received again and within normal range, error is removed.
PFC switch value
When PFC sampling current>PFC open switch current and the DC bus average voltage<PFC open switch voltage,
then opening PFC;
When PFC sampling current<PFC off switch current, off PFC.