207
Smart Power
6.1.10 Timing operation:
1) When using wired controller, unit will be controlled ON/OFF by wired controller
2) When using remote controller, unit will be ON/OFF according to set time by remote controller and current time.
6.1.11 Sleeping function:
1) When using wired controller, unit will be controlled ON/OFF by wired controller
2) When using remote controller, press sleep key to set sleep function including sleeping in heating and sleeping in
cooling. After setting sleeping function and then shift mode, sleeping will recount.
6.1.12 Swing control:
1) When choosing 2HP cassette swing.
When powering on and initializing, it will rstly open to biggest opening for positioning, and then enter basic
opening, fan motor operating after blade moving to right position.
2) When choosing 3-5HP cassette, swinging will be controlled by invisible LED.
It will swing according to default position when rst powering on, and will swing according to swing position
before turning off.
6.1.13 External static pressure setting method
There are 2 ways to achieve the externalstatic pressure setting:
A. by Infrared remote controller ;
B. by wired controller.
MOEDL
Static
pressure
level ( N)
Externalstatic
pressure
Select by Infrared
remote controller
Select by wired
controller
ADH105M1ERG
ADH125M1ERG
ADH140M1ERG
1 30Pa
YR-HBS01 +RE-
02→FAN mode ,fan
speed high→press
HEALTH button 4+N
times(1≤N≤10,integer)
within 12 seconds
Select static
pressure
Level N by
the display
interface
2 40Pa
3 50Pa
4 60Pa
5 70Pa
6 80Pa
7 90Pa
8 100Pa
9 110Pa
10 120Pa
A.By Infrared remote controller
1. Prepare: Infrared remote controller YR-HBS01 , infrared remote receiver RE-02(plug RE-02 connector to indoor
PCB CN29)
2. Method:
Step 1: set the Infrared remote controller at condition: FAN mode ,fan speed high
Step 2: then aim the remote controller at the infrared remote receiver RE-02, press HEALTH button 4+N
times(1≤N≤10,integer) within 12 seconds ,then the receiver will beep N+1 times, the static pressure level N is been
set successfully.
Note: For Infrared remote controller YR-HBS01, need press ON/OFF button make the controller’s at OFF status
rst, then open the button cover press FRESH button will enter FAN mode interface.
Static
pressure
level ( N)
External static
ADH105H1ERG /
ADH125H1ERG /
ADH140H1ERG
1 37
2 50
3 60
4 80
5 100
6 120
7 150
8 170
9 190
10 210