99
Smart Power
Item Model 1UH140P1ERK
Power cable H05RN-F 5G 2.5mm
2
Communication cable /
Connecting cable H05RN-F 4G 2.5mm
2
Power source N, V, Hz 3N~, 380~415, 50/60Hz
Start current A 3
Outdoor
unit
Unit model (color) 1UH125P1ERG (WHITE)
Compressor
Model/Manufacture/place
MNB42FFAMC-L (MITSUBISHI
ELECTRIC COMPRESSOR CO., LTD)
Oil model PVE (FV50S)
Oil charging CC 1600
Type Twin Rotary 1
Fan
Type×Number Axial×2
Speed r/min 700±40
Fan motor input power kW 0.12×2
Fan motor output power kW 0.10×2
Air-ow (H-M-L) m
3
/h 7000
Heat
exchanger
Type/Diameter mm TP2M/Φ7.0
Row/Fin pitch 2 1.4
Total area m
2
1.17
Dimension
External (W×D×H) mm×mm×mm 950×370×1350
Package (W×D×H) mm×mm×mm 1090×480×1500
Drainage pipe (material, I.D./O.D.) mm None
Refrigerant control method mm/mm ELECTRONIC VAVE 3.0mm
Defrosting Auto
Volume of accumulator L 4.0
Sound power Noise level (H-M-L) dB (A) 70
Sound pressure Noise level (H-M-L) dB (A) 53
Type of four way valve SHF-20D-46
Material of reduce noise XPE
Crankcase heater power W 38
Weight (Net/Shipping) kg/kg 108/121
Piping
Refrigerant
Type/Charge g R410A/3700
Maximum pipe length
without recharge refrigerant
30
Recharge quantity g/m 45
Pipe
Liquid mm 9.52
Gas mm 15.88
Connecting method Flared
Between I.D &O.D
MAX. Drop m 30
MAX. Piping length m 75
Norminal condition:
Indoor temperature (cooling) : 27DB (°C)/19WB (°C) , Indoor temperature (heating) : 20DB (°C)
Outdoor temperature (cooling) : 35DB (°C)/24WB (°C) , Outdoor temperature (heating) : 7DB (°C)/6WB (°C)
The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated
sound intensity meter. It is a sound pressure noise level.